Rated insulation voltage Ui
Continuous current
(open and enclosed)
> 200 V
> 230 V
> 460 V
> 575 V
Fig. A
ratings)
AC 600 V
Rated output of three>phase motors at 60 Hz
3TF52..>....1
NEMA/EEMAC
SIZE 4
3TF52
3TF53
A
135
200
210
hp
hp
hp
hp
40
50
100
100
50
60
125
150
60
75
150
200
L1
CIRCUIT
PROTECTIVE
DEVICE
L2
L3
(IF USED)
> Assignment type 1
> Assignment type 2
> non>welding IK< 100¥le
> non>welding IKf100¥le
T1
OLR
T2
M
OLR
T3
(1)
3TF52
3TF53
3TK52
400
250
160
315
400
250
160
315
355
125
>
>
3
PHASE
MOTOR
FUSE
H1
X1
X2
SEC.
FUSE
STOP
Fuse links, gL (gG)
A
A
A
A
OLR
M
PRI.
H4
3TF52/53:
Suitable for use on a circuit capable of delivering not more than 10.000!rms
symmetrical amperes, 600 V max.
Short>circuit protection to
DIN VDE 0660, Part 102 A/IEC 60947>4 **
M
FUSE
IF CPT IS
USED
Horsepower Ratings (
START
(2)
44
(3)
43
M
95
M
A1
OLR
96
A2
2 WIRE CONTROL (IF USED)
Auxiliary circuit
Rated operational current Ie/AC>11
5.6 A at AC 230 V
Short>circuit protection:
> Fuse links
> Circuit breaker
NEOZED and DIAZED
gL (gG), 16 A
C, 10 A
B, 16 A
For further data and accessories see Catalog NSK.
** Footnote:
According to IEC 60947>4/VDE 0660, the types of protection mean:
∫Assignment type 1∫: Short circuits can cause damage to the contactors making replacement of the equipment necessary.
∫Assignment type 2∫ : Easily separable contact welding but no other damage.
3