Download PREFACE - EnviroSpec

Transcript
Step 1. Remove inlet line from fuel unit and install vacuum gage in the
inlet port (see Figure 1). If unit has been running dry, pour oil
into pump prior to testing.
Step 2. Turn burner ON and open bleed.
Step 3. When vacuum reaches 15 in. hg.*, close bleed port.
Step 4. Turn burner OFF. Pump should hold vacuum level for five
minutes*.
*NOTE: If fuel unit cannot attain 15 in. hg. or hold that vacuum level for
five minutes, it should be repaired or replaced.
FUEL UNIT -- TWO-PIPE SYSTEM
FIGURE 2 VACUUM GAGE LOCATION FOR TWO-PIPE SYSTEM
Step 1. Remove inlet line from fuel unit and install vacuum gage in the
inlet port (see Figure 2).
Step 2. Remove return line.
IV-8