[ IX Troubleshooting ]
Error
Code
Error definition and error detection method
6602
Transmission processor hardware error
Although "0" was surely transmitted by the transmission processor, "1" is displayed on the
transmission line
Note: The address/attribute
appeared on the display
on the remote controller
indicates the controller
where an error occurred.
Check method and remedy
(1) When the wiring work of or the polarity of either the indoor or heat source
transmission line is performed or is changed while the power is on, the transmitted data will collide, the wave shape will be changed, and an error will be
detected.
(2) Grounding fault of the transmission line
(3) When grouping the indoor units that are connected to different heat source
units, the male power supply connectors on the multiple heat source units are
connected to the female power supply switch connector (CN40).
(4) When the power supply unit for transmission lines is used in the system connected with MELANS, the male power supply connector is connected to the
female power supply switch connector (CN40) on the heat source unit.
(5) Controller failure of the source of the error
(6) When the transmission data is changed due to the noise on the transmission
line
(7) Voltage is not applied on the transmission line for centralized control (in case
of grouped indoor units connected to different heat source units or in case of
the system connected with MELANS)
Check method and remedy
YES
Is the transmission line work
performed while the power is on?
Turn off the power source of heat source
/indoor units, and turn them on again.
NO
Check the power source of the indoor unit.
NO
208 / 230V?
Faulty power source work
YES
Check the transmission line work is performed
and the shielded wire is treated properly.
Grounding fault or does the shielded
wire contact with the transmission line?
YES
Improper transmission line work
NO
System ?
Single-heat source-unit system
Multiple-heat source-unit system
System with the power supply
unit for transmission lines
Confirm that the power supply
connector on the heat source
unit is not plugged into CN40.
Confirm that the power supply
connector on the heat source
unit is not plugged into CN40.
Is the male power supply connector
connected to the female power supply
switch connector (CN40) on only one
of the heat source unit?
YES
NO
Tightly reconnect the male power
supply connector to the female
power supply switch connector (CN40).
Investigation into the
transmission line noise
Noise exist?
NO
Is the male power supply connector
connected to the female power supply
switch connector (CN40) ?
YES
Disconnect the male
power supply on
CN40 and connect it to CN41
*For the investigation method, follow
<Investigation method of transmission wave shape/noise>
YES
Investigation into the
cause of the noise
NO
Controller failure of the
source of the error
Correct the error.
- 237 -