4. Technical Description
In valve block, pos. 80A, Fig. 4.27, the oil first
passes a stop valve which is normally completely
open. This is not a regulating valve and it is
closed only during maintenance work on the compressor and during cleaning of the filter in the
valve block.
Fig. 4.27
Valve Block, pos. 80A, Oil Return
Inlet
As stated above it is recommended, however, to
keep the solenoid valve closed for 20 to 30 minutes after start-up by means of a time relay (which
may be ordered as an accessory part). Thus the
oil is not returned to the compressor before the oil
separator is warm and has evaporated any refrigerant which may have mixed with the oil at the bottom of the oil separator.
This time function is built into the UNISAB II system.
Nozzle
04 technical description.fm
solenoid valve is open, allowing the oil to flow to
the compressor.
The solenoid valve seat is available with various
boring diameters and nozzle sizes. For this purpose Ø3.3 mm must be used.
The coil for the solenoid valve can be delivered as
a standard part with the following data:
Table 4.2
Outlet
Coil Sizes
220/230 Volt
50/60 Hz
10 Watt
115 Volt
50/60 Hz
10 Watt
240 Volt
50 Hz
10 Watt
Wire mesh
From the stop valve the oil passes a wire mesh,
which can be removed and cleaned.The filtered oil
now passes the solenoid valve, which must be
closed at dead coil whenever the compressor is
stopped. When the compressor is operating, the
0178 - 933 - ENG
Rev. 2005.12.09.
WCaution!
The stop valve is a membrane valve. The membrane can be damaged if the valve is closed too
tight.