Download NotE

Transcript
Test run
Service Manual
6.4.Judgement system for refrigerant amount
¡¡ Before the checking procedure:
1. Operate all the indoor units at the TEST RUN mode and operate all
the indoor units at the HIGH speed.
2. Check the following items in order to make sure that the refrigerant
cycle is stable.
1) The continuous operation lasts more than 20 minutes.
Outdoor air temp. (ºC)
You can check the excess or the deficiency of the refrigerant by means of the data that is provided by the check mode
of the 7-segment display. The following checking procedure is useful during
the test run and the maintenance.
Indoor air temp. (ºC)
2) Td·SH is 25 to 45 ºC in cooling or 15 to 45 ºC in heating
3) Ps is 0.4 to 1.1 MPa in cooling or 0.2 to 1.1 MPa in heating
4) Pd is 2.0 to 3.5 MPa in cooling or 1.6 to 3.5 MPa in heating
Td·SH: Discharge gas temperature superheat
Ps: Suction pressure, Pd: Discharge pressure
3. Collect the checking data that is provided by the check mode of the 7-segment display.
4. Perform the checking according to the following procedure.
Judge according to the following target value:
Cooling
Refrigerant flow charge is controlled by indoor unit expansion valve
Heating
Refrigerant flow charge is controlled by outdoor unit expansion valve
Applicable air temperatures for the checking procedure:
Cooling
Room temperature: 20°C~30°C (DB)
Outdoor temperature: 15°C (DB) or more
Heating
Room temperature: 20°C~30°C (DB)
Outdoor temperature: 0°C~15°C (DB)
¡¡ Checking procedures for cooling
””
Process
1. Convert iE (indoor unit expansion valve opening) with the following table:
Indoor Unit HP
0.8 to 6 HP
8 and 10 HP
Conversion
iE
iE × 2.0
2. Sum up the converted values of iE.
3. Calculate the total frequency (=H1(Inverter frequency))
””
Judgement
- If total of converted iE/Total frequency < 0.7 = Insufficient refrigerant
- If total of converted iE/Total frequency > 1.6 = Excessive refrigerant
56
SMGB0059 rev.0 - 04/2009