Displaying Last 5 Faults FROM FAULT, FIG. 2-3 To display any of the last five faults, press the FAULT button on any GEN STATUS screen. Then press the HIST button on the FAULT screen (Figure 2-5). The FAULT HISTORY screen will display the last Fault Number, a description of the Fault and the hour in total generator set running time when the fault occurred. Press the double arrows [ ] to toggle between the last 5 faults. If there are no faults, the FAULT HISTORY screen will display No Stored Faults. Press [ BACK] to go back to GEN STATUS. Engine Pre-Alarm Screens The PRE-ALARM status lamp will start to blink when engine oil pressure or temperature approaches its limit for engine shutdown. The Display will display Low Oil Pressure or High Engine Temperature on the PRE-ALARM screen (Figure 2-6). OR Press [ BACK] to go back to GEN STATUS to monitor the engine temperature or oil pressure. Service the generator set as required. FIGURE 2-5. FAULT HISTORY FROM FAULT, FIG. 2-3 OR FIGURE 2-6. ENGINE PRE-ALARMS 2-5