Download Instruction Manual AVTM810130 for Capacitance
Transcript
3.9 MEASUREMENT OF APPARATUS BUSHINGS AND CABLE POTHEADS BY HOT COLLAR METHOD (continued) 4. In this test the CL coax lead need not be connected. It can be left off the instrument. 5. Personnel should keep away from the bushing under test to avoid any influence on the readings. 6. Balance the CB100 as described in the "General Operating Instructions" (Section 3.3). FIGURE 22 A breakdown of the different capacitances is shown below. In this test, all three values shown below (C1, C2, C3) are combined. Their values represent the following: C1 - Capacitance between collar and high voltage conductor of bushing ACROSS porcelain surface. C2 - Capacitance between collar and high voltage conductor of bushing THROUGH porcelain and other insulation surrounding the conductor. C3 - Capacitance ACROSS porcelain surface to ground flange. 51