Appendix B
Applications Guide
Circuit Breakers
The most important insulation in medium and high-voltage outdoor power switch gear is
that of the bushings themselves, the guide assembly, the lift rods, and, in the case of oil
circuit breakers, the oil. Measurements should be made from each bushing terminal to
the ground tank with the breaker open, and from each phase (each pair of phase bushing
terminals) to the grounded tank with the breaker closed. When an individual bushing
assembly is tested in each phase, the other bushing terminal in that phase should be
guarded. It is also desirable to test samples of the liquid insulation.
The specific term “tank-loss index” has been developed to assist in evaluating the results
of the open and closed oil circuit breaker tests. It is defined for each phase as the
difference of the measured open circuit and closed circuit power, in watts. To obtain the
open circuit value, the individual values measured on the two bushings of each phase
must be summed. Tank-loss index may have values ranging from positive to negative
which will give an indication of the possible source of a problem. Positive indexes occur
when the closed circuit values are larger than the sum of the open circuit values.
Conversely, negative indexes occur when the closed circuit values are smaller than the
sum of the open circuit values. The test results should be recorded in terms of equivalent
10 kV watts or 2.5 kV watts/milliwatts regardless of the test voltage used. To obtain
watts from a previous measurement of capacitance and dissipation factor, refer to the
conversion formulas.
The Oil Circuit Breakers test data form in Appendix C outlines the specific connections
between the test set and breaker as well as the series of measurements which should be
performed on the breaker.
Table 6, SF6 Dead Tank Circuit Breaker Test Connections, outlines the specific
connections between the test set and breaker as well as the series of measurements that
should be performed on the breaker.
Comparison of tank-loss indexes taken when an oil circuit breaker is new and initially
installed will give the general range of values to expect from a good unit. This practice
also will avoid condemning a good unit as the result of the inherent design of a particular
manufacturer that normally may show tank-loss indexes without the unit being defective
or deteriorated.
The losses in an oil circuit breaker are different between an open circuit test and a closed
circuit test because the voltage stress on the insulating members is distributed differently.
Tables 7 and 8 summarize what may be defective based upon the polarity of the tankloss index. Once a particular section has given indications of deterioration, the test
results should be verified by systematically isolating the suspected insulating member
before disassembling the unit.
Oil circuit breakers are composed of many different materials each having its own
temperature coefficient. For this reason it may be difficult to correct tank-loss indexes
AVTM673001 Rev F Sept 2008
99