Download 673001 - BiddleMegger.com
Transcript
Appendix B Applications Guide Circuit Breakers The most important insulation in medium and high-voltage outdoor power switch gear is that of the bushings themselves, the guide assembly, the lift rods, and, in the case of oil circuit breakers, the oil. Measurements should be made from each bushing terminal to the ground tank with the breaker open, and from each phase (each pair of phase bushing terminals) to the grounded tank with the breaker closed. When an individual bushing assembly is tested in each phase, the other bushing terminal in that phase should be guarded. It is also desirable to test samples of the liquid insulation. The specific term “tank-loss index” has been developed to assist in evaluating the results of the open and closed oil circuit breaker tests. It is defined for each phase as the difference of the measured open circuit and closed circuit power, in watts. To obtain the open circuit value, the individual values measured on the two bushings of each phase must be summed. Tank-loss index may have values ranging from positive to negative which will give an indication of the possible source of a problem. Positive indexes occur when the closed circuit values are larger than the sum of the open circuit values. Conversely, negative indexes occur when the closed circuit values are smaller than the sum of the open circuit values. The test results should be recorded in terms of equivalent 10 kV watts or 2.5 kV watts/milliwatts regardless of the test voltage used. To obtain watts from a previous measurement of capacitance and dissipation factor, refer to the conversion formulas. The Oil Circuit Breakers test data form in Appendix C outlines the specific connections between the test set and breaker as well as the series of measurements which should be performed on the breaker. Table 6, SF6 Dead Tank Circuit Breaker Test Connections, outlines the specific connections between the test set and breaker as well as the series of measurements that should be performed on the breaker. Comparison of tank-loss indexes taken when an oil circuit breaker is new and initially installed will give the general range of values to expect from a good unit. This practice also will avoid condemning a good unit as the result of the inherent design of a particular manufacturer that normally may show tank-loss indexes without the unit being defective or deteriorated. The losses in an oil circuit breaker are different between an open circuit test and a closed circuit test because the voltage stress on the insulating members is distributed differently. Tables 7 and 8 summarize what may be defective based upon the polarity of the tankloss index. Once a particular section has given indications of deterioration, the test results should be verified by systematically isolating the suspected insulating member before disassembling the unit. Oil circuit breakers are composed of many different materials each having its own temperature coefficient. For this reason it may be difficult to correct tank-loss indexes AVTM673001 Rev F Sept 2008 99