Information for Logical Binding
To support the toolbinding configuration, the control units provide the following functions:
• By pressing + and – simultaneously (approx. 2s) or via "Menu -> Service -> Service functions -> Service
PIN", a service PIN message is released.
• The service LED (VL2) on the communication module shows the node status according to the generally
applicable regulations. A second LED (VL1) shows the proper operation of the second communication
module processor by flashing (0.5 sec. on/ 1.0 sec. off).
• When a node receives a wink message, the entire display of the device and all LEDs of the
programming unit flash for one minute or until a button is pressed.
• XIF files can be generated with the binding tool or from the self-documentation of the node.
• At the diagnostic level of the control units, it is possible to see if a device has been bound by selfbinding
or toolbinding. To update this display after toolbinding is complete, the device must first be turned off and
then turned on again.
Overview
A general overview of the connections generated by the Viessmann selfbinding process is illustrated below:
Description
The network variables of the LFDMs of all heating circuit control units (devices
without their own heat generation) are bound to the corresponding network
variables of the system CFDM. Only one CFDM may be active per system.
Between the BoCs and the PM In a multi-boiler system, the network variables of the BoCs are bound to the
of the system
corresponding network variables of the PM1 ... PM4 (starting with PM1).
Between the fault manager
The nviNodeAlarm network variables of the control unit designated as the fault
and all other devices of the
manager, as well as one of the network variables nviNodeAlarm1 to
system
nviNodeAlarm5 of the Vitocom 300, if present, receive data from the nvoAlarm
network variables of all devices in the system.
Between the time of day
The nvoNodeTimeSet network variable of the device designated as the time
information sender and the
sender is bound to the nviNodeTimeSet network variables of all other devices in
time of day information
the domain.
receiver
Between the outdoor
The network variable nvoNodeOATemp of the device which is to send the
temperature sender and the
outdoor temperature is bound to the network variable nviNodeOATemp of all
outdoor temperature receiver
other units of the system.
5719 291 GB
Connections
Between all LFDMs and the
CFDM of the system
76