Download CONDENSING UNITS

Transcript
5. Electric Characteristics
Model
Outdoor Unit
Power Supply
Compressor
OFM
Hz
Voltage
Min.
Max.
MCA
TOCA
MFA
MSC
RLA
KW
FLA
ASE-76AH
50
380-415
342
438
17.5
18
20.5
86
16.5
0.573
2.613
ASE-96AH
50
380-415
342
438
20
21
23.8
110
20
1.373
6.26
ASE-120AH
50
380-400
342
440
25
28.6
30
147
21.4
1.373
6.26
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (kW)
6. Operation Limits
Temperature range for unit operation:
Cooling mode
Item
Model
All model
Heating mode
Outdoor
Indoor
Outdoor
Indoor
21℃~52℃
17℃~32℃
-10℃~24℃
20℃~27℃
13