Download - DairyNZ
Transcript
5 SYSTEM DESIGN The third stage in developing a farm dairy effluent (FDE) system is to select components and create detailed plans describing how the system will achieve the design specifications. System specifications are also prepared, listing what the final system will comprise of, and what it will be capable of achieving. 5.1 Land Application System Selection A land application system must be selected that meets or exceeds all of the requirements of the design specifications. Application depth and application intensity are the key specifications likely to drive the selection process. However, the system must also be suitable for the farming enterprise type, and meet any other client needs. Special emphasis should be given to providing a system that is capable of a low application intensity and a low application depth where soil and landscape features dictate this as beneficial. Because of the nutrient content of FDE, it is especially important for FDE irrigation to be applied with high uniformity. Highly uniform application maximises the nutrient benefit to pasture and avoids potential adverse effects on water quality. Special emphasis should also be given to selecting components that are able to handle the solids content of FDE without blockages. Note the section on Special Considerations for the Application of Separated Solids. Adjusting Application Depth for Uniformity The design specification for application depth (Section 4.3) needs to be adjusted for the application uniformity of the selected system. The application depth, adjusted for uniformity, must still be less than the depth listed in the design specification. Make this adjustment prior to preparing the final system specification. An upper quartile distribution uniformity (DUuq) is recommended as a measure of FDE land application uniformity. DUuq is a measure of uniformity that focuses on the one quarter of the application area that receives the highest applied depth (Duq – see Figure 4). Therefore, minimising DUuq means minimising over-application of FDE while maximising the mean depth that can safely be applied. DUuq is calculated by: DUuq = Duq / Davg (7) where: DUuq = Upper quartile distribution uniformity Duq = Mean depth of FDE applied to the one-quarter of the area receiving the greatest depth Davg = Mean depth of FDE applied to the whole area Farm Dairy Effluent (FDE) Design Code of Practice – September 2015 Page 24