Download Foreword
Transcript
VF5000 series high capacity vector control inverter service manual Set range 0000—1111(0: Forward 1: Reverse) F7.01~F7.10 are to set frequency, direction, Acc/Dec time of PLC stages. When the PLC operating direction is determined by operating commands, the motor’s operating direction can be changed by external command. For example, running forward can be ordered by terminal FWD-COM. The direction is decided by running command and if it cannot be determined, the drive will runs in the direction of last operating stage. F7.11 Traverse operation control mode Set range Factory default 000 0000—111 LED first bit: Reserved LED second bit: Traverse control 0: Fixed Traverse amplitude 1: Changing wobble amplitude LED third bit: Stopping mode of traverse operation 0: Start as earlier state 1: Restart LED forth bit: Save parameters upon power-off 0: Save 1: Not save F7.12 Traverse preset frequency Set range F7.13 Factory default 0.00Hz—upper limit frequency Waiting time before traverse Set range 10.00Hz Factory default 0.0s 0.0—3600.0s F7.12 defines the frequency before entering traverse state. When the traverse start, F7.13 specifies the time period that the drive run at preset traverse frequency. F7.14 Traverse amplitude Set range Factory default 0.0—50.0% Varied amplitude: AW=central frequency×F7.14 Fixed amplitude: AW=max. frequency F0.06×F7.14 - 69 - 10.0%