Download TECHNICAL DATA & SERVICE MANUAL
Transcript
Design of W-2WAY ECO-i SYSTEM Unit Specifications 2. System Design Indoor unit changes The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank. Outdoor unit Selected model Type 1405+0905 Type 604 Type 484 Type 484 Type 254 15.0 / 16.5 13.0 / 14.5 13.0 / 14.5 5.5 / 6.2 73.0 / 81.5 16.0 / 18.0 14.0 / 16.0 14.0 / 16.0 7.30 / 8.00 59.36 / 58.45 16.00 / 18.00 14.00 / 16.00 13.42 / 15.69 6.82 / 7.71 16.00 / 18.00 14.00 / 16.00 13.42 / 15.69 6.82 / 7.71 Maximum load (cooling/heating) (kW) Rated capacity (cooling/heating) (kW) (5) Corrected capacity (cooling/heating) (kW) Room 1 Room 2 Room 3 Room 4 (indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4) (7) Actual capacity (cooling/heating) (kW) Total corrected capacity of all indoor units (cooling/heating) = 50.24/57.4 Ruc = 50.24/59.36 = 0.846 < 1 Ruh = 57.4/58.45 = 0.982 < 1 For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load. Selection is completed. (2) Calculate the final selection results according to the capacity calculation procedure. 1 [From calculation of the correction coefficient to calculation of actual capacity] 2 3 Rated capacity (kW) 73.0 / 81.5 Correction coefficient Outdoor unit 1.00 / 1.00 (1) Model Room 1 Room 2 Room 3 Room 4 (indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4) 16.0 / 18.0 14.0 / 16.0 14.0 / 16.0 7.30 / 8.00 (2) Temp. condition 1.019 / 0.941 0.934 / 0.964 0.934 / 0.964 0.934 / 0.964 0.934 / 0.964 (3) Tubing length, elevation difference 0.798 / 0.856 1.105 / 1.070 1.079 / 1.052 1.026 / 1.018 1.00 / 1.00 (4) Frosting/defrosting 0.89 1.032 / 1.031 1.008 / 1.014 0.958 / 0.981 0.934 / 0.964 1.03 / 1.03 1.01 / 1.01 0.96 / 0.98 0.93 / 0.96 16.00 / 18.00 14.00 / 16.00 13.42 / 15.69 6.82 / 7.71 Result of (2) × (3) Correction coefficient applied to indoor unit *1 (5) Corrected capacity (kW) *2 4 (Cooling/heating) 59.36 / 58.45 (6) Correction coefficient for corrected capacity ratio (7) Actual capacity (kW) 1.00 / 1.00 16.00 / 18.00 14.00 / 16.00 13.42 / 15.69 6.82 / 7.71 *1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)). *2: Corrected outdoor unit capacity = Rated outdoor unit capacity × (1) × (2) × (3) × (4) 5 6 The actual capacity is calculated as shown below. Cooling: Ruc = (16.0 + 14.0 + 13.42 + 6.82) / 59.36 = 0.846 < 1 Therefore, Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit (In other words, the correction coefficient (6) for the corrected capacity ratio is 1.) Heating: Ruh = (18.0 + 16.0 + 15.69 + 7.71) / 58.45 = 0.982 < 1 Therefore, Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit × (0.1 × Ruh + 0.9) / Ruh (In other words, the correction coefficient (6) for the corrected capacity ratio is (0.1 × Ruh + 0.9) / Ruh.) 7 8 2-18