ELECTRICAL DATA
Model No.
HP29−090−2
Line voltage data 60 hz − 3 phase
HP29−120−2
208/230v
460v
575v
208/230v
460v
575v
Rec. max. fuse or circuit breaker size (amps)
60
30
25
80
40
25
{Minimum circuit ampacity
39
20
15
53
25
18
Rated load amps
28.8
14.7
10.8
37.8
17.2
12.4
Locked rotor amps
195
95
80
239
125
80
Full load amps (total)
3
1.5
1.2
2.4 (4.8)
1.3 (2.6)
1 (2)
Locked rotor amps (total)
6
3
2.9
4.7 (9.4)
2.4 (4.8)
1.9 (3.8)
C
Compressor
(1)
Outdoor Coil
FanMotor (1 phase)
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus and minus 10% of line voltage.
HACR type (under 100 amps). U.S. only.
ELECTRICAL DATA
G
General
D
Data
Model No.
Line voltage data − 60 hz − 3 phase
Compressor (1)
Outdoor Coil
Fan Motor (1 phase)
FanMotor
HP29−090−3
HP29−120−3
208/230v
460v
575v
208/230v
460v
575v
Rec. max. fuse or circuit breaker size (amps)
60
35
25
80
40
25
{Minimum circuit ampacity
40
21
16
53
25
18
Rated load amps
28.8
14.7
10.8
37.8
17.2
12.4
Locked rotor amps
195
95
80
239
125
80
Full load amps (total)
3.7
1.9
1.6
2.4 (4.8)
1.3 (2.6)
1 (2)
Locked rotor amps (total)
7.3
3.7
3.4
4.7 (9.4)
2.4 (4.8)
1.9 (3.8)
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus and minus 10% of line voltage.
HACR type (under 100 amps). U.S. only.
Page 3