FHPP
Where variable speed control of motors is required, they are to be provided with Variable
Frequency Drives (VFD) as follows:
Each motor is to be controlled by a dedicated VFD which is also to provide motor protection
for overcurrent and loss of phase along with the normal facilities provided by the
manufacturer as standard. The VFD is to have the facility to control the motor speed in
response to a 0 to 10V signal from the B.M.S. Run and Trip lamps are to be provided on
the panel fascia and the operating status is to be monitored by the B.M.S. An
“ON/OFF/AUTO” selector switch is be provided for each motor on the control panel fascia.
When at “AUTO”, the motor is to be started and stopped by the B.M.S. Each VFD is to be
provided with a T.P.& N. contactor-controlled power supply from the control panel.
The motor speed is to be monitored by the B.M.S.
When at “ON”, the motor is to run at a speed which is to be manually adjustable at the
VFD's keypad.
The VFDs are to be as manufactured by Danfoss Ltd., and are to be provided by the
Controls Sub-Contractor. They are to be suitable for either panel or field mounting as
specified later.
(b)
Sequenced Starting
Where the instantaneous starting currents of all motors, etc., connected to a control panel
would exceed the capacity of the fuses provided on the electrical supply to the control
panels, delay timers are to be provided to reduce the maximum instantaneous current as
necessary, when started under automatic control, or by the Fireman's switches.
Sequential starting is to be provided also to ensure that the plant starts in an orderly and
safe manner and the correct conditions are met before starting plant.
(c)
Thermal Controls
Unless otherwise later specified in any particular instance, every control circuit which
automatically controls temperature, humidity, etc., in any air or water system, (other than 2position control loops), is to incorporate a proportional- plus-integral-plus-differential
modulating controller mounted in the control panel of the plantroom concerned. Setpoints
are all to be fully adjustable. Proportional band, integral action rate and differential rate are
to be adjusted to optimum settings to match the characteristics of the plant concerned. If
the Controls Sub-Contractor considers that superior control will be achieved by an integral
action controller, then this may be offered as an alternative; it should have fully adjustable
setpoint and integral action rate.
Where individual controllers are used for the various control functions, they are to be flushmounted onto the face of the control panels. Where a composite programmable controller
is used, a keyboard and back-lit display for monitoring and adjusting the operation of the
systems that are controlled are to be permanently mounted on the front of each control
panel.
All thermostats, sensors, actuators, control valves, etc., are to be individually labelled with
'Traffolyte' labels using the reference numbers contained within this Specification.
All settings of all controls are to be fully adjustable.
Y:\00-Enquires\E4340\4.0 FHP Specifications\4.8 Combined M&E\E4340 M&E Technical Specification.docx