Download Scroll Plus Rack System Manual
Transcript
Return to Contents ELECTRICAL 4-2 September 1, 1997 WIRING GUIDELINES BASED ON VARIOUS COMPONENTS Check the store legend for components requiring electrical circuits to either the compressor unit or the defrost control panel. These include: – Defrost termination thermostat – Thermostat controlling a header mounted liquid line solenoid – CDA temperature control – ETR temperature control – Satellite control All thermostat and temperature sensor wires should be sized for pilot duty at 120VA 120VAC. Run a 2wire circuit for each system using any of the five controls listed above. Unit Cooler Fan Wiring Provide a 120/1/60 fused power supply for each cooler. (Check the store legend to see if 208230/1/60 is required at this location.) Evaporator Mounted Liquid Line Solenoid Power for a liquid line solenoid in the case can be picked up from the fan circuit. (Check fan motor and solenoid voltages first.) Select Wire Size Based on the serial plate ampacity of the system, select the largest connectable wire size from Table 1. Cooler Door Switch Wiring Check the store legend for door switch kits (M115 or M116). The switch must be mounted to the cooler door frame, and must be wired to control the field installed liquid line solenoid and the fan circuit. For Koolgas applications, kit M116 includes a check valve to bypass the liquid line solenoid valve. Sizing Wire and Overcurrent Protectors Check the serial plate for Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protective Devices (MOPD). Follow NEC guidelines. Defrost Controls These circuits may be repeated and/or intermixed in one store. Other Controls When other controls are used, refer to the manual included with that control. Table 4-1 — Required Field Wire Size TOTAL CONNECTED MCA* LARGEST CONNECTABLE WIRE (Based on no more than 3 wires in the raceway and 30OC environment per NEC.) 75O C Wire Rating 50OC 140A (max) 00 per Phase 248A (max) 350 mcm per Phase 408A (max) 2 x (250 mcm) per Phase 608A (max) 2 x (500 mcm) per Phase *Include control circuit amps if single point connection transformer option is used 12A for 208V systems 6A for 460V systems (Refer to NEC for temperature derating factors.) HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 • Printed in USA