Technical manual LMC340i
function is always enabled. Off means the function is
disabled
• Default Off
• T
he compressor speed limit during start is disabled
during oil return compressor start. Liquid line valve is
opened during oil return in suction pressure control
mode
Oil return frequency
9.23. Installer – Limiter alarms
Number of limiter activations per day before an alarm is
set active.
17-01-2012
Lim. Alarms
Relay action Tc-Tdis-Current
Relay action To
09:31
10
Off
• Compressor frequency (FI) during oil return operation
• Range 25 Hz. – 87 Hz.
• Default 70 Hz.
Oil return interval
• Minimum time since last oil return start
• Range 1 h. – 48 h.
• Default 4 h.
Evap. Limiter off
Relay action Tc-Tdis-Current
• Allowed number of alarms without activating the CTS
alarm relay
• T
ime the compressor is allowed to run with unchanged
frequency even if TO is below the Evaporating temp. min.
limiter setting
• Valid for Condensing temp. max.
• Range 0 sec. – 30 sec.
• Range 0 – 999. 0 = Off
• Default 0 sec.
• Default 10
Run time
Relay action To
• Run time with Oil return frequency speed
• A
llowed number of alarms without activating the CTS
alarm relay
• Range 0 sec. – 180 sec.
• Default 30 sec.
• Discharge gas temp. max. and FI current limiters
• Valid for Evaporating temp. min. limiter
• Range 0 – 999. 0 = Off
• Default Off
Page 49