Baycrest Centre for Geriatric Care Apotex Building 5th Floor HHA #2151048-01 Section 23 31 13 Ductwork Page 13 of 18 .6 Maintain set of drawings on site, coloured each day during testing to indicate extent of duct satisfying leakage criteria under test. .7 Submit a written report, verified by TAB Agent, identifying each segment of duct system tested, showing calculation of allowable leakage, test pressure and leakage value measured under test, and certifying that leakage testing has been satisfactorily completed. 3.10 Duct cleaning .1 Cleaning to be performed by agent specializing in this field of work, be a member in good standing with National Air Duct Cleaners Association (NADCA), and to comply with NADCA standards. .2 Clean new horizontal and vertical ducts (supply, return, exhaust, transfer), as well as, existing supply and return ductwork connected to new fan systems. .3 Clean ductwork using high powered vacuum system, hand tools and mechanical brushing systems such that metal surfaces are visibly clean. .4 Reset balancing dampers to original settings if moved during work. Have TAB Agent confirm damper settings. .5 Maintain set of drawings on site, coloured each day during cleaning to indicate extent of duct cleaning completed. .6 Submit a written report, verified by TAB Agent, identifying extent of duct system cleaning and certifying that NADCA standards have been met. 3.11 Fitting Illustrations .1 Illustrations of fitting referenced in this specification follows in Annex A. Issued For Tender