Section 20 07 19
Piping Insulation
Page 12 of 15
Baycrest Centre for Geriatric Care
Apotex Building 5th Floor
HHA #2151048-01
.1 On vertical pipes arrange circumferential overlap on adjacent sheets outside of sheet below and
under sheet above.
.3 PVC sheeting :
.1 Hot piping:
(a) overlap longitudinal edges and adjacent sheets by minimum of 50 mm (2 in) and staple
fasten the sheets.
(b) secure sheeting with colour matched tape around circumference, at least two places per
section of sheet, and by stapling longitudional and circumferential edges.
(c) do not seal edges with vapour barrier tape.
(d) seal PVC fitting covers at throat and heel seams by stapling and secure over insulation by
banding or taping ends to adjacent pipe finish covering with colour matched tape.
.2 Cold and Dual Temperature piping:
(a) overlap longitudinal edges and adjacent sheets by minimum of 50 mm (2 in) and seal
longitudinal edges with vapor barrier coating adhesive for full depth and 100% coverage of
overlap,
(b) seal circumferential edges of PVC fitting covers with reinforced vapour barrier coating
adhesive extending over adjacent pipe insulation section with an overlap of at least 50 mm (2
in).
(c) seal PVC fitting covers at throat and heel seams by solvent bonding and secured over
insulation with reinforced vapor barrier coating/mastic overlapping adjacent pipe insulation a
minimum of 50 mm (2 in).
3.12
Mechanical Damage Protection - Indoors
.1 Protect exposed pipe insulation extending up through a floor sleeve at floor line with 1.2 mm (18 ga)
stainless steel jacket approximately 100 mm (4 in) high, secured to floor slab. Conceal fastenings by
floor plate.
.2 For piping systems using metal finishes, this protection cover replaces a portion of the specified pipe
cover.
.3 For piping systems using other finishes, this protection cover is in addition to the specified pipe cover.
3.13
Field Quality Control
.1 The Consultant reserves the right to have protective finish coverings removed on up to 5% of all
fittings, flanges, couplings, valves, and pipeline accessories to review the sealing of the insulation, at
no change in cost.
.2 If insulation sealing is found to be incorrect at any one location, remove the protective finish on all
fittings, flanges, couplings, valves, and pipeline accessories for review.
.3 Repair defective sealing and replace protective coverings at no change in cost.
3.14
Insulating and Finishes Tables
.1 Table 1, 2 and 3 follows.