Download WARNING CAUTION IMPORTANT IMPORTANT

Transcript
Electrical Data
208/230V−60 Hz−1 Ph
Unit
Compressor
Condenser Fan
Maximum
Over−
current
Protection
(amps)1
Minimum
Circuity
Ampacity2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
XC16−024−230−01
20
13.6
10.25
52.0
1/10
1075
0.7
1.4
XC16−024−230−02
20
13.6
10.25
52.0
1/6
825
1.1
1.87
Model Number
Locked Rotor
Amps (LRA)
208/230V−60 Hz−1 Ph
Unit
Compressor
Condenser Fan
Maximum
Over−
current
Protection
(amps)1
Minimum
Circuity
Ampacity2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
XC16−036−230−01
35
22.0
16.67
82.0
1/6
825
1.1
2.1
XC16−036−230−02
35
22.0
16.67
82.0
1/6
825
1.1
1.87
XC16−036−230−03
35
22.0
16.67
82.0
1/10
825
1.1
1.87
Model Number
Locked Rotor
Amps (LRA)
208/230V−60 Hz−1 Ph
Unit
Compressor
Condenser Fan
Maximum
Over−
current
Protection
(amps)1
Minimum
Circuity
Ampacity2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
XC16−048−230−01
45
28.2
21.15
96.0
1/4
825
1.7
3.1
XC16−048−230−02
45
28.2
21.15
96.0
1/4
825
1.7
3.1
Model Number
208/230V−60 Hz−1 Ph
Unit
Compressor
Condenser Fan
Maximum
Over−
current
Protection
(amps)1
Minimum
Circuity
Ampacity2
Rated Load
Amps (RLA)
Locked
Rotor
Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
XC16−060−230−01
55
33.9
25.64
118.0
1/3
825
1.8
2.9
XC16−060−230−02
55
33.9
25.87
118.0
1/3
825
1.8
2.9
Model Number
1 HACR
2 Refer
type circuit breaker or fuse.
to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 3
XC16 SERIES