Download File
Transcript
• If hardware input two is closed, the IQ System Controller indexes the system to the input 2 Position Setpoint (In2Closed = 75). • If both input one and input two are closed, the IQ System Controller indexes the system to the closed reference setpoint (Closed = 100). Option GF5, Building Pressure Control (Range -0.5 to 2.5” w.c.) On a command to start, the IQ System Controller enables the damper and modulates the damper to maintain the Building Pressure Setpoint (PressSP = 0.5). The IQ System Controller modulates the damper open on a drop in building pressure and closed on a rise. The control application uses a proprietary control loop to maintain the pressure setpoint. The IQ System Controller limits the adjustable outside air damper between a minimum setpoint (MinPos = 25) and a maximum setpoint (MaxPos = 100). Option GF6, Mixed Air Control by CO2 (Range 200 to 2000 ppm) On a command to start, the IQ System Controller enables the damper and modulates the damper to maintain the CO2 Level Setpoint (CO2SP = 800). The IQ System Controller modulates the fan speed up on a rise in the CO2 level and down on a decrease. The control application uses a proprietary control loop to maintain the pressure setpoint. The IQ System Controller limits the adjustable outside air damper between a minimum setpoint (MinPos = 25) and a maximum setpoint (MaxPos = 100). Option GF7, Two Position Outside Air Enthalpy Control (Range 15 to 40 btu/lb of dry air) On a command to start, the IQ System Controller enables the damper and indexes the damper to a fixed position based on the outside air (OA) enthalpy changeover setpoint (OAE Chgover = 28). When the OA enthalpy is above the changeover setpoint, the IQ System Controller indexes the damper to the High OA Enthalpy Damper Setpoint (HiDAE Pos = 50). When the OA enthalpy is below the changeover setpoint, the IQ System Controller indexes the damper to the Low OA Enthalpy Damper Setpoint (LoOAS Pos = 100). Option GF8, Dual Reference Enthalpy Control Option D15: The mixed air temperature (MAT) setpoint is the discharge air temperature setpoint (NA SP = 70) minus the Mixed Air Temperature Offset (MAT Offset = 1). Option D16: The mixed air temperature setpoint is a constant value. Default setpoint is 55°F (MAT SP = 55). Setpoint can be adjusted. Application of Option GF8 - applies to Options D15 and D16: The dual reference enthalpy control sequence will be enabled upon proof of fan. The dampers will be modulated by the IQ System Controller between the required position open and 100% under the ventilation/recirculation and economizer application program as follows: Condition 1: Outside air temperature < the mixed air temperature setpoint and the return air enthalpy > the outside air enthalpy plus 2. Under this condition, the IQ System Controller modulates the dampers to maintain the mixed air temperature (MAT) setpoint. Condition 2: Outside air temperature > mixed air temperature setpoint and outside air enthalpy < return air enthalpy minus 2. Under this condition, the OA dampers will be 100% open and the RA damper shall be fully closed. Condition 3: Outside air enthalpy > return air enthalpy minus 2. Under this condition, the outside air damper will be at its required position for minimum flow and the return air damper will be at its corresponding position open. Option GF9, Dry Bulb Economizer Control Option D15: The mixed air temperature (MAT) setpoint is the discharge air temperature setpoint (NA SP = 70) minus the Mixed Air Temperature Offset (MAT Offset = 1). Option D16: The mixed air temperature setpoint is a constant value. Default setpoint is 55°F (MAT SP = 55). Setpoint can be adjusted. Application of Option GF9 - applies to Options D15 and D16: The dual reference enthalpy control sequence will be enabled upon proof of fan. The dampers will be modulated by the IQ System Controller between the required position open and 100% under the ventilation/recirculation and economizer application program as follows: Form CP-MAPS-D15/D16/D17/D18, P/N 254003R8, Page 15