9.0 Network
9.1 General
The IQ System supports BACnet over MS/TP, BACnet over ARCnet, and LonWorks
for Building Automation System (BAS) integration. The LonWorks protocol requires
an optional plug-in communication card (Option BHB5) and preprogramming of the
controller while the BACnet protocol is standard on the controller. The IQ System controller on a MAPS® unit is shipped as standard with the BACnet over MS/TP active
and configured with a 9600 baud rate, 12345 MSTP network number, and 2402 device
instance address. The speed, network number, and device instance are all field selectable.
NOTE: Units are NOT field convertible to LonWorks.
9.2 Protocols
Protocols are the communication languages spoken by control devices. The main
purpose of a protocol is to provide a standard communication link between control
devices to allow information to be passed in the most efficient method possible. The
IQ controller has the ability to speak multiple protocols to allow seamless integration
to any Building Automation System. For two devices to communicate with each other,
they must speak the same protocol or have a protocol translator. A protocol is defined
as follows:
•A set of formal rules describing how to transmit data.
o Low level protocols define
□□ the electrical and physical standards to be observed
□□ bit-and-byte-ordering
□□ the transmission, error detection, and correction of the bit stream
o High level protocols deal with data formatting, including
□□ syntax of messages
□□ terminal-to-computer dialogue
□□ character sets
□□ sequencing of messages, etc.
• It is a language spoken between electronic devices
o Example: the protocol IP, which stands for Internet Protocol.
9.3 BACnet
BACnet, which stands for Building Automation and Controls Network, is a protocol
developed by ASHRAE. BACnet was developed as a response to industry concerns
about increased networking of Building Automation Systems components using proprietary communication methods. In many instances, these proprietary communications severely limited system expansion, upgrade, and replacement. BACnet has been
accepted as an open standard by the American National Standards Institute (ANSI)
and the European CEN standards. It is also being adopted as an international ISO
standard. BACnet is designed to include all building systems, including lighting, security, fire, heating, ventilation, and air conditioning.
It is important to understand the BACnet communication protocol contained in the IQ
control system in a Reznor® MAPS® unit. The BACnet information in the following paragraphs is designed to assist in the understanding of the basics of how a Reznor® unit
interfaces with a front-end Building Automation System (BAS). There needs to be an
understanding of Reznor® equipment responsibility versus the responsibility of the control contractor. This section will explain a few points of interest and define the BACnet
interface between the Reznor® IQ system and a typical controls front-end BAS. The
following is a short breakdown of the target points that are covered.
 Overview of the BACnet communications protocol
o Short definition of the needed variables and their general application

Overview of requirements for the Reznor® IQ control system to successfully
interface with a BACnet front-end BAS control system
o Setting of network specific variables to make the Reznor® IQ system
compatible and ready for BACnet interfacing. (MS/TP, Device ID, and IQ
Controller Device Instance)
Form CP-MAPS-D15/D16/D17/D18, P/N 254003R8, Page 55