Download Man CTA_1-6
Transcript
2) cooling and humidification, control is performed according to the table below, based on the whether the priority is set for temperature or humidity. Temperature request Heating Humidity request Dehumidification Cooling Humidification Preheating coil TEMPERATURE PRIORITY Cooling coil Based on temperature control probe Off Off Based on temperature control probe Reheating coil Humidifier If “integration” cascade control Off Off Waits for temperature set point to be reached Note: in the case of request of cooling and dehumidification the control considers the greater than the two required on the cooling coil. Temperature request Heating Humidity request Dehumidification Cooling Humidification Preheating coil HUMIDITY PRIORITY Cooling coil Waits for humidity set point to be reached Acts on saturated probe set point if humidifier = adiabatic Based on humidity control probe Waits for humidity set point to be reached Reheating coil Humidifier If “compensation” acts on supply Off due to cooling Off Based on humidity control probe 8.6 Set point compensation Mask index Display description Set point compensation adjusts the set point defined by the user with an offset that depends on a probe. This function in some cases ensures energy saving by adapting the set point to the outside temperature, while still guaranteeing suitable values for comfort. A temperature set point of 23 °C for example can be adjusted to 21 °C when the climate is extreme. In other cases, it’s used to: 1) improve comfort, reducing the difference between the outside temperature and the inside or room temperature; 2) integrate another air-conditioning system: for example, if in summer at 7 in the morning the outside temperature is lower than the room temperature, the room probe can be used as the compensation probe and the supply probe as the control probe to lower the set point and exploit freecooling. The following are possible: 1) differentiate between compensation in summer and winter; 2) select the probe used for compensation, between outside, supply, return and room probe; 3) increase or decrease the set point being compensated. Hc01 Main regulation probe selection Temperature Return ¦ supply ¦ room Type of summer set point None ¦ external ¦ room ¦ compensation supply ¦ return Compensation delta 2 °C Compensation start 25 °C Compensation end 32 °C Type of winter set point None ¦ external ¦ room ¦ compensation supply ¦ return Compensation delta -2 °C Compensation start 0 °C Compensation end -8 °C Gfc08 Gfc09 8.7 Summer/winter changeover This changeover can be performed from the keypad, digital input or supervisor (BMS), based on the heating/cooling coil temperature or automatically. Summer/winter changeover switches the control set point from summer to winter. The basic function involves switching from cooling in summer to heating in winter. If “Auto” cool/heat is active (Gfc04) both heating and cooling are possible in summer and winter. Note: compensation is disabled if the control probe and the compensation probe are the same. Below is an example with the compensation probe set as the outside temperature probe that compensates the room temperature set point. SetT_comp SetT_comp SetT Gc02 Gfc04 SetT delta < 0 delta < 0 Start_comp End_comp SetT-delta Season selection from Keypad ¦ Digital input ¦ B.M.S ¦ Keypad /B.M.S. ¦Auto ¦ H2O Temperature Auto ¦ Fix days End_comp Start_comp Key Temperature set point Compensation delta Start compensation +030220921 - rel. 1.0 - 28.02.2011 End_comp End compensation B1 SetT_comp Compensation probe Compensation set point Set season Temperature regulation Auto cool/heat No ¦ Yes For automatic season changeover, on screen Gc01 and Gc02 the season must be selected as “Auto”. Automatic selection allows the changeover to be managed “actively”, in the sense that for one month before and one month after the set date the season changeover can be brought forward or postponed if the outside temperature remains above or below a certain level for a certain set time in hours (both to enter and exit the function, eliminating swings in system operation). This allows a temporary change in season (and corresponding set point) without having to act manually to adapt for days with uncharacteristic outside temperatures for that period. B1 B1 Delta Start_comp Selection delta > 0 delta > 0 SetT Display description SetT+delta SetT+delta SetT-delta Mask index Gc01 WINTER SUMMER Selection 42