2) cooling and humidification,
control is performed according to the table below, based on the whether the priority is set for temperature or humidity.
Temperature
request
Heating
Humidity
request
Dehumidification
Cooling
Humidification
Preheating coil
TEMPERATURE PRIORITY
Cooling coil
Based on temperature control
probe
Off
Off
Based on temperature
control probe
Reheating coil
Humidifier
If “integration”
cascade control
Off
Off
Waits for
temperature set
point to be reached
Note: in the case of request of cooling and dehumidification the control considers the greater than the two required on the cooling coil.
Temperature
request
Heating
Humidity
request
Dehumidification
Cooling
Humidification
Preheating coil
HUMIDITY PRIORITY
Cooling coil
Waits for humidity set point to be
reached
Acts on saturated probe set point if
humidifier = adiabatic
Based on humidity
control probe
Waits for humidity set
point to be reached
Reheating coil
Humidifier
If “compensation”
acts on supply
Off due to cooling
Off
Based on humidity
control probe
8.6 Set point compensation
Mask index
Display description
Set point compensation adjusts the set point defined by the user with
an offset that depends on a probe. This function in some cases
ensures energy saving by adapting the set point to the outside
temperature, while still guaranteeing suitable values for comfort. A
temperature set point of 23 °C for example can be adjusted to 21 °C
when the climate is extreme. In other cases, it’s used to:
1) improve comfort, reducing the difference between the outside
temperature and the inside or room temperature;
2) integrate another air-conditioning system: for example, if in
summer at 7 in the morning the outside temperature is lower than
the room temperature, the room probe can be used as the
compensation probe and the supply probe as the control probe to
lower the set point and exploit freecooling.
The following are possible:
1) differentiate between compensation in summer and winter;
2) select the probe used for compensation, between outside, supply,
return and room probe;
3) increase or decrease the set point being compensated.
Hc01
Main regulation probe selection
Temperature
Return ¦ supply ¦ room
Type of summer set point None ¦ external ¦ room ¦
compensation
supply ¦ return
Compensation delta
2 °C
Compensation start
25 °C
Compensation end
32 °C
Type of winter set point
None ¦ external ¦ room ¦
compensation
supply ¦ return
Compensation delta
-2 °C
Compensation start
0 °C
Compensation end
-8 °C
Gfc08
Gfc09
8.7 Summer/winter changeover
This changeover can be performed from the keypad, digital input or
supervisor (BMS), based on the heating/cooling coil temperature or
automatically. Summer/winter changeover switches the control set
point from summer to winter. The basic function involves switching
from cooling in summer to heating in winter. If “Auto” cool/heat is
active (Gfc04) both heating and cooling are possible in summer and
winter.
Note: compensation is disabled if the control probe and the
compensation probe are the same.
Below is an example with the compensation probe set as the outside
temperature probe that compensates the room temperature set
point.
SetT_comp
SetT_comp
SetT
Gc02
Gfc04
SetT
delta < 0
delta < 0
Start_comp
End_comp
SetT-delta
Season selection from
Keypad ¦ Digital input ¦ B.M.S ¦
Keypad /B.M.S. ¦Auto ¦ H2O
Temperature
Auto ¦ Fix days
End_comp
Start_comp
Key
Temperature set
point
Compensation delta
Start compensation
+030220921 - rel. 1.0 - 28.02.2011
End_comp
End compensation
B1
SetT_comp
Compensation probe
Compensation set
point
Set season
Temperature regulation
Auto cool/heat
No ¦ Yes
For automatic season changeover, on screen Gc01 and Gc02 the
season must be selected as “Auto”. Automatic selection allows the
changeover to be managed “actively”, in the sense that for one
month before and one month after the set date the season
changeover can be brought forward or postponed if the outside
temperature remains above or below a certain level for a certain set
time in hours (both to enter and exit the function, eliminating swings
in system operation). This allows a temporary change in season (and
corresponding set point) without having to act manually to adapt for
days with uncharacteristic outside temperatures for that period.
B1
B1
Delta
Start_comp
Selection
delta > 0
delta > 0
SetT
Display description
SetT+delta
SetT+delta
SetT-delta
Mask
index
Gc01
WINTER
SUMMER
Selection
42