Download Modbus ASCII Slave
Transcript
Mode of Operation of the Data Link Parameters 3.2 The parameters and operating modes listed below must be set for the loadable driver using the parameter assignment tool. • Transmission rate, parity • Slave address (Modbus) of CP • Operating mode (normal, interference suppression) • Character delay time • Address areas for FC01, 05, 15 • Address areas for FC02 • Base DB number for FC03, 06, 16 • Base DB number for FC04 • Ranges for write access Task Distribution Task Distribution Modbus function codes 01, 02, 03, 04, 06, and 16 are processed by the CP directly. For function codes 05 and 15 the communications FB81 carries out data input into the SIMATIC memory area bit-by-bit. 3.3 Used Modbus Function Codes Used Function Codes The following Modbus function codes are supported by the driver: Function Function in accordance General Description Codes with Modbus Specification 01 Read Coils Read bits 02 Read Discrete Inputs Read bits 03 Read Holding Registers Read registers (words/dwords) 04 Read Input Registers Read registers (words) 05 Write Single Coil Write 1 bit 06 Write Single Register Write 1 register (word/dword) 08 Diagnostic Subfunction 0 only, echo rcvd word 15 Write Multiple Coils Write multiple contiguous bits 16 Write Multiple Registers Write multiple contiguous registers (words/dwords) Loadable Driver CP341: MODBUS ASCII Slave with 32-Bit Extensions 6ES7870-1CA00-0YA0; Manual Edition 1.0 3-2