Download IRDH275 - Bender

Transcript
IRDH275
Installation Bulletin / Reference Guide
TM
Menu Structure Flow Chart
Front Panel Display
Figure 5 shows the structure of the menu built into the IRDH275. The menu is used for viewing
alarms, viewing the status of the system, and making any necessary settings changes.
Use the supplied gray boxes to take note of applied settings for future reference.
Menu or settings option
Settings option essential for proper operation
Settings option only available with IRDH275B
1
1. EXIT
2. HISTORY INFO
3. ISO SETUP
1. Exit
2.Alarm1
1 kΩ... 10 MΩ
3. Alarm2
1 kΩ... 10 MΩ
4. K1
N/O-T N/C-T
N/C N/O Flash
5. K2
N/O-T N/C-T
N/C N/O Flash
Memory
on
7. M+/M-
0-20 mA
4-20 mA
off
3
4
2.AGH
no 150 204 520S
3. Ce max
150 500
4. Measure
AMP DC
5. Autotest
24 no 01
6. Clock
00:00
7. Date
dd.mm.yy
8. Test
00:00 ... 23:00
2. Addr.
1 ... 30
3. ISONet
on off
4. ISO Monitor
1 ... 30
INFO / ESC key: Displays system information / goes back a step in menu
5.
LED “ALARM 1”: Illuminates when alarm
1 is active.
2.
TEST / UP key: Initiates self-test / moves
up in menu
6.
LED “ALARM 2”: Illuminates when alarm
2 is active.
3.
RESET / DOWN key: Resets device when
latching mode is active / moves down
in menu
7.
LED “ERROR”: Illuminates when a device
error has occured.
4.
MENU / ENTER key: Opens the main
menu / confirms changes in menu
Standard IRDH275 models feature a 0 - 400 μA analog output based on the measured insulation resistance. IRDH275B models feature a 0 - 20 mA or 4 - 20 mA output, selectable in the
main menu under ISO SETUP > M+/M-. For integrating the analog outputs into control systems, refer to the equations below for the type of analog output being used.
0 - 400 μA output
Insulation resistance in kΩ
Current output in μA
RF
I
Insulation resistance in kΩ
Current output in mA
RF
I
Insulation resistance in kΩ
Current output in mA
4 - 20 mA output
2. Password
000 ... 999
3. Status
on off
1. Exit
7. LANGUAGE
RF
I
0 - 20 mA output
1. Exit
6. PASSWORD
6 7
1.
1. Exit
5. COM SETUP
5
Analog Outputs
1. Exit
4. ISO ADVANCED
2
Ordering Information
English Deutsch
2. Text
IRDH275
8. SERVICE
B
W
1
1
-
435
2
Figure 5 - IRDH275 menu flow chart
Technical Data
Code 1: Optional features
Refer to IRDH275 series user manual (document TGH1361en) or IRDH275 series datasheet
(document NAE1012020) for detailed technical information.
Modifier
Nothing
"B"
"W"
"BW"
Dimensions
Dimensions in inches (mm).
Additional features
Standard device
Real-time clock with history memory, 0(4) - 20 mA output
Additional vibration protection, greater temperature range
Both features of the "B" and "W" above
4.4” (112.5)
Code 2: Auxiliary supply voltage
Ø 0.18”
(4.5)
2.9” (74)
Modifier
3.2” (81)
4.1”
(105)
4.1”
(105)
"435"
"425"
"427"
Supply voltage US (absolute values)
DC 77…286 V / AC 42…460 Hz 88…264 V
DC 10.2…36 V
DC 19.2…72 V
Figure 3 - IRDH275 dimensions in inches (mm)
Bender Inc. • USA: 800.356.4266 / 610.383.9200 / info@bender.org • Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com • www.bender.org