Download IRDH275 - Bender
Transcript
IRDH275 Installation Bulletin / Reference Guide TM Menu Structure Flow Chart Front Panel Display Figure 5 shows the structure of the menu built into the IRDH275. The menu is used for viewing alarms, viewing the status of the system, and making any necessary settings changes. Use the supplied gray boxes to take note of applied settings for future reference. Menu or settings option Settings option essential for proper operation Settings option only available with IRDH275B 1 1. EXIT 2. HISTORY INFO 3. ISO SETUP 1. Exit 2.Alarm1 1 kΩ... 10 MΩ 3. Alarm2 1 kΩ... 10 MΩ 4. K1 N/O-T N/C-T N/C N/O Flash 5. K2 N/O-T N/C-T N/C N/O Flash Memory on 7. M+/M- 0-20 mA 4-20 mA off 3 4 2.AGH no 150 204 520S 3. Ce max 150 500 4. Measure AMP DC 5. Autotest 24 no 01 6. Clock 00:00 7. Date dd.mm.yy 8. Test 00:00 ... 23:00 2. Addr. 1 ... 30 3. ISONet on off 4. ISO Monitor 1 ... 30 INFO / ESC key: Displays system information / goes back a step in menu 5. LED “ALARM 1”: Illuminates when alarm 1 is active. 2. TEST / UP key: Initiates self-test / moves up in menu 6. LED “ALARM 2”: Illuminates when alarm 2 is active. 3. RESET / DOWN key: Resets device when latching mode is active / moves down in menu 7. LED “ERROR”: Illuminates when a device error has occured. 4. MENU / ENTER key: Opens the main menu / confirms changes in menu Standard IRDH275 models feature a 0 - 400 μA analog output based on the measured insulation resistance. IRDH275B models feature a 0 - 20 mA or 4 - 20 mA output, selectable in the main menu under ISO SETUP > M+/M-. For integrating the analog outputs into control systems, refer to the equations below for the type of analog output being used. 0 - 400 μA output Insulation resistance in kΩ Current output in μA RF I Insulation resistance in kΩ Current output in mA RF I Insulation resistance in kΩ Current output in mA 4 - 20 mA output 2. Password 000 ... 999 3. Status on off 1. Exit 7. LANGUAGE RF I 0 - 20 mA output 1. Exit 6. PASSWORD 6 7 1. 1. Exit 5. COM SETUP 5 Analog Outputs 1. Exit 4. ISO ADVANCED 2 Ordering Information English Deutsch 2. Text IRDH275 8. SERVICE B W 1 1 - 435 2 Figure 5 - IRDH275 menu flow chart Technical Data Code 1: Optional features Refer to IRDH275 series user manual (document TGH1361en) or IRDH275 series datasheet (document NAE1012020) for detailed technical information. Modifier Nothing "B" "W" "BW" Dimensions Dimensions in inches (mm). Additional features Standard device Real-time clock with history memory, 0(4) - 20 mA output Additional vibration protection, greater temperature range Both features of the "B" and "W" above 4.4” (112.5) Code 2: Auxiliary supply voltage Ø 0.18” (4.5) 2.9” (74) Modifier 3.2” (81) 4.1” (105) 4.1” (105) "435" "425" "427" Supply voltage US (absolute values) DC 77…286 V / AC 42…460 Hz 88…264 V DC 10.2…36 V DC 19.2…72 V Figure 3 - IRDH275 dimensions in inches (mm) Bender Inc. • USA: 800.356.4266 / 610.383.9200 / info@bender.org • Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com • www.bender.org Document NAE1018020 • 10.2012 • © Bender Inc. • Page 1/1 • Side 2/2