14 Function library primo.lib
MotorOff
PMCprimo-Command: MO (Motor off)
Function library: Positioncontrol
Description:
This function block switches off the controller release. All other functions remain active, the
encoder signals are evaluated. In case the controller release is re-activated, the motor remains in
the instantaneous position.
In case of an open position control loop the setpoint signal is damped with 0V with the
PMCprimo 2+2/16+ and the relay of the axis opens. This relay should be used as controller or
drive release. The relay simultaneously damps the setpoint output with 0V. In case the motor
controller is locked with the relay, the motor coasts freely.
This function can also be used as alternative Stop-Command. With the function GlobalOff (see
page 177) the function MotorOff can be executed at all axes at the same time.
Input variables:
bExecute (BOOL)
usiNode (USINT)
usiChannel (USINT)
The motor is switched off in case of a change from 0 to 1
0 resets the function block and the output variables
are set to False or 0
The node number in the linked system, 0 if only one unit or Host
The axis number from 1 to n (depending on the system)
Output variables:
bDone (BOOL)
Motor is switched off (True) or module is still under operation (False)
bError (BOOL)
True: an error has occurred; False: no error
iErrorNumber (INT) Indicates the exact error cause (see GetError page 203)
Connected function
MotorOff und GlobalOff
Examples:
Declaration:
INST: MotorOff;
bVarBOOL1: BOOL;
bVarBOOL2: BOOL;
Example in IL:
CAL
LD
ST
INST(bExecute := bVarBOOL1, usiNode := 0, usiChannel := 1)
INST.bDone
bVarBOOL2
Example in ST:
INST(bExecute := bVarBOOL1, usiNode := 0, usiChannel := 1);
bVarBOOL2:=Inst.bDone;
Example in FBD:
Page 180
User Manual PMCprimo SoftPLC