FX3U/FX3UC Series PLC User's Manual - Analog Control Edition
1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
A
Connectable PLC and Its Version Number
Common Items
1.3
1.3 Connectable PLC and Its Version Number
PTW-ADP is compatible with the following PLC.
Compatible PLC
Date of production
Ver. 2.20 or later
After May 2005 (initial production)
FX3UC Series PLC
Ver. 1.30 or later
After August 2004
B
FX3U-4AD
FX3UC-4AD
Version number
FX3U Series PLC
1. Version check
Special data register D8001 contains information for determining the PLC version.
2
4
1
0
FX3U-4AD-ADP
D8001
C
0
PC type and
version number
Version data (Example: Ver. 1.00)
PC type (Example: 24 = FX2N, FX3U, FX2NC, and FX3UC series)
D
FX3U-4DA
2. How to look at the manufacturer's serial number
The year and month of production of the product can be seen from the manufacturer's serial number
"SERIAL" indicated on the label adhered to the right side of the product.
Example:
FX3U-48MR/ES(production number : 570001)
MITSUBISHI
MODEL
FX3U-4DA-ADP
Right side
E
PROGRAMMABLE
CONTROLLER
FX3U-48MR/ES
100-240VAC 50/60Hz 40W
OUT:30VDC/240VAC 2A(COSφ=1)
SERIAL
F
570001
FX3U-4AD-PT
-ADP
80M1 IND. CONT. EQ.
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
5
7
0
0
0
1
1.4
Compatible Programming Tool Version Number
H
Remarks
Ver. SW8 P or later
(Ver. 8.13P)
When selecting a model, select FX3U(C)*1.
I
PID Instruction
(FNC 88)
GX Developer
• SW D5C-GPPW-J
• SW D5C-GPPW-E
Version number
If a programming tool with the wrong version number is used, programming will not be possible.
*1.
FX3U-4AD-TC
-ADP
Use the programming tool with the following version number to create programs for PTW-ADP of the FX3U/
FX3UC Series PLC:
Software
G
FX3U-4AD-PTW
-ADP
Control number
Month (Example: 7 = July), 1 to 9 = January to September,
X = October, Y = November, Z = December
Year (Example: 5 = 2005), last digit of dominical year
For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.