Download Installation and Sizing

Transcript
Sizing/Selection
Characterized Control Valves™ (CCV)
3-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
Cv
Maximum
Rating
Inches
DN
mm
3-Way
CCV
Pressure Drop Across the Valve
1 psi
2 psi
3 psi
4 psi
5 psi
6 psi
7 psi
8 psi
9 psi
10 psi
0.3
0.46
0.8
1.2
1.9
3
4.7
10
4.7
7.4
24
7.4
10
30
10
19
25
19
29
37
46
29
37
46
57
68
83
½”
½”
½”
½”
½”
½”
½”
½”
¾”
¾”
¾”
1”
1”
1”
1¼”
1¼”
1¼”
1½”
1½”
1½”
1½”
2”
2”
2”
2”
2”
2”
15
15
15
15
15
15
15
15
20
20
20
25
25
25
32
32
32
40
40
40
40
50
50
50
50
50
50
B307(B)
B308(B)
B309(B)
B310(B)
B311(B)
B312(B)
B313(B)
B315(B)*
B317(B)
B318(B)
B320(B)*
B322
B323
B325*
B329
B330
B331
B338
B339
B340
B341
B347
B348
B349
B350
B351
B352
0.3
0.5
0.8
1.2
1.9
3.0
4.7
10
4.7
7.4
24
7.4
10
30
10
19
25
19
29
37
46
29
37
46
57
68
83
0.4
0.7
1.1
1.7
2.7
4.2
6.6
14
6.6
10
34
10
14
42
14
27
35
27
41
52
65
41
52
65
81
96
117
0.5
0.8
1.4
2.1
3.3
5.2
8.1
17
8.1
13
42
13
17
52
17
33
43
33
50
64
80
50
64
80
99
118
144
0.6
0.9
1.6
2.4
3.8
6.0
9.4
20
9.4
15
48
15
20
60
20
38
50
38
58
74
92
58
74
92
114
136
166
0.7
1.0
1.8
2.8
4.2
6.8
11
22
11
17
54
17
22
67
22
43
56
43
65
83
103
65
83
103
128
152
186
0.7
1.1
2.0
2.9
4.7
7.3
12
24
12
18
59
18
24
73
25
47
61
47
71
91
113
71
91
113
140
167
204
0.8
1.2
2.1
3.2
5.0
7.9
12
26
12
20
63
20
26
79
27
50
66
50
77
98
122
77
98
122
151
180
220
0.8
1.3
2.3
3.4
5.4
8.5
13
28
13
21
68
21
28
85
28
54
71
54
82
105
130
82
105
130
161
192
235
0.9
1.4
2.4
3.6
5.7
9.0
14
30
14
22
72
22
30
90
30
57
75
57
87
111
138
87
111
138
171
204
249
0.9
1.5
2.5
3.8
6.0
9.5
15
32
15
23
76
23
32
95
32
60
79
60
92
117
146
92
117
146
180
215
263
K20903 - 04/08 - Subject to change. © Belimo Aircontrols (USA), Inc.
GPM = Cv x ∆p * = Models with no characterizing disc.
The influence of the pipe geometry due to reduced flow is negligible for all valves 83 Cv and below with characterizing discs.
800-543-9038 USA
4
866-805-7089 Canada
203-791-8396 Latin America