CHAPTER8 PARAMETERS
1
(9) I/O assignment
The mounting status of each module in the system is set.
2
3
4
5
6
7
Figure 8.9 I/O assignment
8
Table8.9 I/O assignment setting list
Item
Parameter
No.
Base
setting
Setting range
Set the model name of the mounted
module. (Entered at user’s discretion.
Do not use the one for the CPU
module.)
Up to 16 characters
Points
Set the number of points assigned to
each slot.
0, 16, 32, 48, 64, 128, 256, 512, or
1024 points
Start XY
Set the start I/O number of each slot.
0H to FF0H
Base model
name
Set the model name of the main base
unit or extension base unit. (Entered at
user’s discretion. Do not use the one
for the CPU module.)
Up to 16 characters
Power model
name
Set the model name of the power
supply module on the main base unit
or extension base unit. (Entered at
user’s discretion. Do not use the one
for the CPU module.)
Up to 16 characters
Extension
cable
Set the extension cable name.
(Entered at user’s discretion. Do not
use the one for the CPU module.)
Up to 16 characters
Slots
Set the number of slots of the main
base unit or extension base unit.
This setting must be done for all base
units.
2, 3, 5, 8, 10, or 12
0401H
Reference
• CPU No.2 to No.4: No.n/Empty (Set
"CPU (Empty)" for the slot where no
CPU module is mounted.)
• Empty, Input, Hi input, Output,
Intelli., I/O mix, or Interrupt
Model name
0400H
Default
Blank
Section
4.2.2
Blank
Section
4.1.2
(To the next page)
8 - 12
8.1 PLC Parameters
Set the type of the mounted module.
Type
I/O
Assignme
nt
Description