Coils, Contacts and Interconnects
Normal Coil
A normal coil is a discrete output shown as a 0x reference.
A normal coil is ON or OFF, depending on power flow in the program.
A ladder logic network can contain up to seven coils, no more than one per row.
When a coil is placed in a row, no other logic elements or instruction nodes can
appear to the right of the coil’s logic-solve position in the row. Coils are the only
ladder logic elements that can be inserted in column 11 of a network.
To define a discrete reference for the coil, select it in the editor and click to open a
dialog box called Coil.
Symbol
????
WARNING
Forcing of Coils
When a discrete input (1x) is disabled, signals from its associated input
field device have no control over its ON/OFF state. When a discrete
output (0x) is disabled, the PLC’s logic scan has no control over the ON/
OFF state of the output. When a discrete input or output has been
disabled, you can change its current ON/OFF state with the Force
command.
There is an important exception when you disable coils. Data move and
data matrix instructions that use coils in their destination node
recognize the current ON/OFF state of all coils in that node, whether
they are disabled or not. If you are expecting a disabled coil to remain
disabled in such an instruction, you may cause unexpected or
undesirable effects in your application.
When a coil or relay contact has been disabled, you can change its
state using the Force ON or Force OFF command. If a coil or relay is
enabled, it cannot be forced.
Failure to observe this precaution can result in severe injury or
equipment damage.