8. SHIPPING AND MOUNTING
Transport the heat meters only on fully enclosed vehicles and with protection against shifting and damage. Store the heat meters in unit packaging in dry, clean indoor areas above +5 °C and below 90%
of relative humidity. The heat meter can be identified (traced) by the markings and technical data located on the enclosure label. The shipment addressee should inspect the condition of the parcel before
unpacking the heat meter, especially:
• the condition of the packaging;
• completeness of the shipment;
• the types and versions against the order;
• the condition of the enclosure and its seals (see section 8.1).
The heat meters are delivered only as complete units with the sensor pair installed where one sensor
is installed in the flow transducer enclosure and the other in the pipe tee installed in the heat pipe. The
quick user manual must be enclosed with the product. Check the heat meter for mechanical damage
before installation. If any damage, missing parts or discrepancies against the specifications is found,
send a claim for the affected unit. The product must be installed in the heating system piping by a professional service and according to the design requirements of the building and of PN-EN 1434-6:2007.
The flow direction shown by the arrow on the flow transducer body must match the actual flow in the
metering circuit. The heat meter must be installed in the correct pipe (supply or return) as indicated
on the sticker on the enclosure. If the heat meter is installed in the supply circuit, mount the supply
temperature sensor in the flow transducer body and the return sensor in the return line, and vice versa,
i.e. if the heat meter is in the return circuit, install the supply temperature sensor in the supply line and
the return sensor in the flow transducer enclosure. Seal the heat meter connections on both lines with
the same sealing wire threaded through the holes in the threaded connections and through the special
lug on the flow transducer body. The following figure is an example of installation and sealing of the
heat meter on the return line
Return
Supply