Electrical water valve The plug of the water valve should be connected using the black cable supplied with the unit (see the illustration below). Water valve connection After connecting the black cable to the plug for the magnetic valve, the other side of the cable should be led through the feed-through rubber at the side of the unit. Subsequently, the two connections should be connected to the appropriate terminals (terminal N and terminal 7) on the terminal strip. Water leakage sensor The electrical compartment contains a loose, 5m long white wire: the water leakage sensor. This sensor should be led to the outside through the opening and should be placed on the ground at the lowest point. The end of the sensor cable can be split into several cores using a connector, so that more than one point is secured against leakage. If the sensor has a black cap, this should be cut off and the cores should be stripped 5 mm. The other side should be connected to the little white plug on the printed circuitboard (see the illustration below). In case of water leakage, the water supply will be stopped immediately by means of the electrical valve in the water pipe. 3