Analog Output, Menu 36
The analog output controls a variable speed fan. Enter the
approximate output voltage using this menu to check the variable
speed fan. Note: the value will disappear from the display upon
entering it.
Water Pulse, Menu 37
This input is dedicated to water meter use. Menu 37 shows
the current pulse count, and should change if water is flowing.
Scales, Menu 38
This menu allows testing the scales. Place a known weight
on the scale; the value will show in the display.
Note: the internal algorithms that check for stable bird
weights may cause the tare to reset while weighing multiple birds.
This will not cause the readings to be off since the AC-2000HP
keeps track of the number of birds on the scale. The display will
change after a brief delay, when a bird gets off, or a new one gets
on. If the bird remains stable on the scale, the display will change
to zero. Then, if it comes off the scale, the display will show the
negative value of its weight.
Calibration
Temperature, Menu 41
Check and calibrate each temperature sensor with menu 41.
To calibrate, stabilize the sensors at a known temperature, then enter that temperature.. The AC-2000HP will calculate the
calibration factor. If you know the calibration factor, you can enter
it directly.
Instead of measuring air temperature for calibration, it is
simpler to measure the temperature of a pail of water. Air temperature changes rapidly in small regions by several degrees as air
currents move, making calibration difficult. Starting with the water
temperature near ‘brood’ temperature provides the most accurate
temperatures at the most sensitive time in the birds life. Make sure
to stir the water well while measuring to eliminate hotter and cooler
regions (stratification).
Scales, Menu 42
Calibrate the bird scales with menu 42. While keeping the
scale empty (no birds on it), enter menu 42, and select the scale to
calibrate. Allow at least five seconds to give the AC-2000HP time