H ow ever, if one of these three values is unknow n, this equation cannot be used d irectly.
In m any cases, the unknow n value is gross cooling capacity at rated cond itions. In this
case, it is necessary to calculate supply fan p ow er, w hich is d irectly related to supply
fan heat. If supply fan heat is know n, then the gross capacity can be calculated by
ad d ing supply fan heat to net cooling capacity to get gross cooling capacity, and
equation (11) can be u sed .
If supply fan heat (or pow er) at rated cond itions is not know n, then the calculations
becom e m ore com plex. The supply fan pow er at rated cond itions can be calculated in
the follow ing m anner:
(12)
πΆπΉπ‘€π‘Ÿπ‘Žπ‘‘π‘’π‘‘ × π‘†π‘ƒπ‘‘,π‘Ÿπ‘Žπ‘‘π‘’π‘‘
𝐡𝐻𝑃𝑠𝑒𝑝𝑝𝑙𝑦 ,π‘Ÿπ‘Žπ‘‘π‘’π‘‘ =
βˆ’π‘–π‘› 𝐻2𝑂
6,356[𝐢𝐹𝑀 𝑏𝑕
] × πœ‚π‘“π‘Žπ‘›
𝑝
w here
𝐡𝐻𝑃𝑠𝑒𝑝𝑝𝑙𝑦 ,π‘Ÿπ‘Žπ‘‘π‘’π‘‘
The supply fan pow er at rated conditions (bhp)
πΆπΉπ‘€π‘Ÿπ‘Žπ‘‘π‘’π‘‘
The supply airflow at rated conditions (CFM)
𝑆𝑃𝑑,π‘Ÿπ‘Žπ‘‘π‘’π‘‘
The total static pressure at rated conditions (in H 2O)
πœ‚π‘“π‘Žπ‘›
The com bined efficiency of the fan and m otor at rated conditions
Where the above values are know n, the fan pow er can be calcu lated easily. H ow ever, if
the above values are not available, som e assu m ptions are necessary.
When the rated supply airflow is not know n, a typical value of 350 CFM/ ton can be
used and the airflow is calculated to be:
πΆπΉπ‘€π‘Ÿπ‘Žπ‘‘π‘’π‘‘ =
𝑄𝑑,π‘Ÿπ‘Žπ‘‘π‘’π‘‘
12
π‘˜π΅π‘‘π‘’
𝑕 βˆ’π‘‘π‘œπ‘›
(13)
×
𝐢𝐹𝑀
350[ π‘‘π‘œπ‘› ]
w here 𝑄𝑑,π‘Ÿπ‘Žπ‘‘π‘’π‘‘ is the AH RI rated capacity of the proposed unit in kBtu/ h.
To d eterm ine the total static pressure of the system at rated cond itions, it is necessary to
know both the internal and external static pressures at rated cond itions.
Internal static at rated cond itions (π‘†π‘ƒπ‘–π‘›π‘‘π‘’π‘Ÿπ‘›π‘Žπ‘™ ,π‘Ÿπ‘Žπ‘‘π‘’π‘‘ ) should includ e the packaged unit w ith
w et coil and no filters. If not entered by the user from m anufacturer’s d ata, it is
assum ed to be 1.00 in. H 2O. This value has been estim ated based on d ata from several
m anufacturers’ packaged unit catalogs.
Energy Mod el Inp u t Pre-Processor User’s Gu id e
14