Download Safety Manager Software Reference

Transcript
Communication via the Experion protocol
Communication via the Experion protocol
The Experion™ protocol is used for non-safe data communication on controller
level.
Function
The Experion™ protocol is used on physically connected Safety Managers to:
•
Write the states of non-safe inputs with location COM.
•
Monitor the states of each Safety Manager point.
•
View Safety Manager diagnostics and system parameters on an Experion
Station.
•
collect SOE data.
For more information see “Sequence of events (SOE)” on page 441.
•
synchronize the Safety Manager real-time clock.
See “Real-time clock synchronization” on page 332 for details.
Experion
Note:
For details on Experion communication and Experion FTE, see the Experion Safety
Manager Integration Guide in the Experion Knowledge Builder.
The Experion™ protocol is based on the PlantScape protocol that runs on
Ethernet. It is primary used for communication between Experion servers and
clients, such as stations, CEE controllers and Safety Manager.
Communication
Note:
1. The Experion protocol runs on top of an Ethernet TCP/IP layer.
2. With the Experion protocol you can only communicate to physically directly
connected Safety Managers.
The Experion™ protocol can be run:
Safety Manager Software Reference
299