Download not CS 50

Transcript
Setting
Temperature ⎢Neutral zone ⎢
Parameter name
Setting range
Cooling – heat exchanger(Hrec) -5,0...5,0
Unit
°C
(not CS 50)
(Hrec)Heat exchanger - Heating
-5,0...5,0
°C
4.51 Speed Stage 1, Supply Air
Description
Sets the desired speed for stage 1.
This applies only to units that have infinitely variable fan control.
Setting
Fan control I Speed setting I Supply air I Speed 1
Parameter name
Setting range
Unit
Default value
Speed 1
0…100%
%
35
4.52 Speed Stage 2, Supply Air
Description
Sets the desired speed for stage 2.
This applies only to units that have infinitely variable fan control.
Setting
Fan control I Speed setting I Supply air I Speed 2
Parameter name
Setting range
Unit
Default value
Speed 2
0…100%
%
50
4.53 Speed Stage 3, Supply Air
Description
Sets the desired speed for stage 3.
This applies only to units that have infinitely variable fan control.
Setting
Fan control I Speed setting I Supply air I Speed 3
Parameter name
Setting range
Unit
Default value
Speed 3
0…100%
%
100
4.54 Speed Stage 1, Extract Air
Description
Sets the desired speed for stage 1.
This applies only to units that have infinitely variable fan control.
Setting
Fan control I Speed setting I Extract air I Speed 1
Parameter name
Setting range
Unit
Default value
Speed 1
0…100%
%
35
47/67
FLEXIT AS
CS 50/CS 500 User Manual
94269