HPB INTEGRATED PROTECTION RELAY USER MANUAL
Issue: R5, Date: 6/2011
Symptom
Cause
Remedy
The relay‟s MCI input is not
closing (level 6 position 2).
Check that main contactor is closing. If not check
circuit.
Check auxiliary contacts and wiring.
Check system voltage display (level 4, position 1)
as contactor closes. Compare this with the under
voltage threshold.
Relay will not remain
closed and cycles while the
start input is held closed.
Relay not receiving voltage
feedback on all three outlet
phases within 800mS of
contactor closing.
Check continuity from the relay, through the
CCMB - 6.6 kV to power conductors.
WARNING!
Be sure to follow the
appropriate high voltage
isolation procedures.
HPB 6.6kV Typical reading: CCMB - 6.6K 27
Meg Ohm
Main contactor fail
condition.
Check main contactor for leakage across
terminals on frozen contactor condition.
Flat or faulty battery.
AA cell installed under the top cover requires
replacement. The owner in a workshop
environment can replace a direct replacement
battery.
It is recommended that the relay be returned to
Ampcontrol for battery replacement and full
testing.
Time and date incorrect.
Resets to 1/01/9? on power
up.
Low battery.
AA cell installed under the top cover requires
replacement. The owner in a workshop
environment can replace a direct replacement
battery.
It is recommended that the relay be returned to
Ampcontrol for battery replacement and full
testing.
HDM Displays “Hardware
fault”.
CCMB has not been
detected.
Check all wiring to the CCMB and earthing.
Relay Trips on MCF on
power up.
HPBB012R5.docx
Page 32