Chapter 5 Analog Modules SMART I/O User’s Manual O_SET_LINE_LIMIT: This operate call allows the user to set the open loop detect level on the current version of the SM-ADC1. The syntax is as follows: <analog var> := OPERATE(<iovar>, O_SET_LINE_LIMIT, <var>); where <analog var> represents the analog return variable and can be zero if the operate call is supported and the correct <iovar> is passed or non-zero if an error occurred. <iovar> is the variable name for the channel where the operate call is to take effect. <var> is the current value in mA and calculated using the following formula: var = 0xFFF0 mA 0x14 O_GET_LINE_STATE: This operate call allows the user to check the line state on the current version of the SM-ADC1. The syntax is as follows: <analog var> := OPERATE(<iovar>, O_GET_LINE_STATE, <var>); where October 01, 1996 <analog var> represents the analog return variable and is zero if an open loop is detected. Otherwise it returns 1. <iovar> is the variable name for the channel where the operate call is to take effect. <var> is not used. ©1996 PEP Modular Computers GmbH Page 5 - 105 5