Download GS 50A01A10-01EN - Dcs

Transcript
14
<<Contents>> <<Index>>
Alarm and Events
ALARM/FAST allows alarms to be presented on a number of different devices, like:
• Web HMI Servers & Clients
• Printers
• Paging systems (pagers, SMS, telephone)
• Acoustic devices (horns)
On Web HMI Servers & Clients the alarm presentation will, in most cases, be a real-time alarm table in a frame with
scroll bars containing significant information for the operator. Additionally, graphical objects to which the alarms apply
can be configured to change color, shape, position etc.
F09E.ai
In ALARM/FAST the alarm information can be customized for each device. Generally speaking the alarm text line will
contain information regarding:
• Alarm priority (0-15)
• Alarm status (Alarm, Event, Acknowledged, reset, normal, etc)
• Date and time of the alarm (generated by FAST/TOOLS or via the timestamp received from the PLC or RTU, down
to milliseconds)
• Item name, value, description and alarm description
• Alarm status text (Low, Low-Low, High, High-High, normal, underrange, overrange, offline, blocked, etc.)
Alarms are presented in two ways:
• Dynamically on display and/or printer (current alarms)
• Historical (chronological in time) on display and/or printer Historical alarms can be archived on disk or external
storage.
Current alarms can be presented in a scalable frame with scrollbar controls that for example can be defined as a
separate current alarm display or a three line banner at the bottom of the page. This overview is dynamic by nature;
if an alarm no longer exists and is acknowledged (manually or automatically) then the alarm disappears from the
screen. If there are no alarms active, this display or banner is empty. Every column of the alarm text line can be used
to sort the alarm list so that current alarms can be sorted in:
• Priority base order
• Time base order
• Alarm status order
• Etc.
All Rights Reserved. Copyright © 2008, Yokogawa Electric Corporation
GS 50A01A10-01EN May 28, 2010-00