Section 8 Setting data Auxiliary output 1 non-exciting Auxiliary output 2 non-exciting Auxiliary output 3 non-exciting Auxiliary output 4 non-exciting l.3 sb1n sb2n sb3n sb4n • These settings are used to select the output state of alarms 1, 2, 3, and 4. Function • When close in alarm is selected, the state of the alarm output function is output without change. When open in alarm is selected, the state of the output function is inverted before output. The relation between the alarm output function, alarm output, and operation indicator is shown below. Setting data Auxiliary output function Auxiliary output Operation indicator ON ON On OFF OFF Off ON OFF On OFF ON Off Close in alarm Open in alarm Setting Setting data Reference 8-58 Setting data Setting range Auxiliary output 1 non-exciting Auxiliary output 2 non-exciting Auxiliary output 3 non-exciting Auxiliary output 4 non-exciting n-o: Close in alarm n-c: Open in alarm Units − Default value n-o: Close in alarm ● Related setting data "Bank ∗ alarm ∗" (Bank setting level) (P.8-28) "Bank ∗ alarm upper limit ∗ ", "Bank ∗ alarm lower limit" (Bank setting level) (P.8-29) "Auxiliary output ∗ assignment" (Control initial setting level 2) (P.8-48) "Alarm ∗ type" (Alarm setting level) (P.8-54) "Alarm ∗ latch" (Alarm setting level) (P.8-55) "Alarm ∗ hysteresis" (Alarm setting level) (P.8-56) "Standby sequence restart" (Alarm setting level) (P.8-57)