2.5.2
2-stage burner
Release burner stage 1
In the case of single-boiler plants, the burner stage of the 1-stage boiler will be released as
soon as a valid boiler temperature setpoint becomes active. (Refer to Generation of the
boiler temperature setpoint, page 12).
Release burner stage 2
If the required boiler temperature setpoint cannot be attained with the first burner stage, the
second burner stage will be released (release integral satisfied). When the second burner
stage is released, the first burner stage stays active, but setpoint control will be ensured by
the second stage. The first stage can be switched off again only when the second stage is
locked (reset integral satisfied).
The second burner stage is released by a heat deficit integral. This differential is considered
for integration if the boiler temperature is below the switch-on point (TKx < TKw-SDK/2)
when the first burner stage is switched on. The second burner stage is released if the
integral reaches the value set in the parameters.
Release integral
°C
TKx
TKw+SDK/2
52
50
TKw
a
TKw-SDK/2
2371Z32
48
46
tF
44
t
a
TKw
TKx
SDK
t
tF
Reset integral
The second burner stage is locked by a heat surplus integral. This differential is considered
for integration if the boiler temperature is above the switch-off point (TKx > TKw+SDK/2).
The second burner stage is locked if the integral reaches the value set in the parameters.
°C
TKx
b
52
TKw+SDK/2
50
TKw
48
TKw-SDK/2
46
2371Z34
Locking burner stage 2
Release integral
Boiler temperature setpoint
Actual value of the boiler temperature
Switching differential of the boiler
Time of day
Release time
tR
44
t
b
TKw
TKx
SDK
t
tR
Reset integral
Boiler temperature setpoint
Actual value of the boiler temperature
Switching differential of the boiler
Time of day
Reset time
14/164
Siemens Schweiz AG
HVAC Products
Basic documentation ALBATROS2 range
2 Oil / gas boiler
CE1P2359en
22 September 2006