Download DTSC-200 Series Interfaces Interface Description
Transcript
Manual 37389 DTSC-200 Series - Interfaces Description of the DTSC Parameters ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ DE EN Interfaces: General Device number Gerätenummer CAN bus: Device number 1 to 127 So that this control unit may be positively identified on the CAN bus, the unit address must be set in this parameter. The address may only be represented once on the CAN bus. All other addresses on the CAN bus are calculated on the basis of the address entered in this parameter. CL2 1702 NOTE If the protocol is CANopen, the Node ID is defined with the device number. NOTE DE EN The CAN bus is a field bus and subject to various disturbances. Therefore, it cannot be guaranteed that every request will be answered. We recommend to repeat a request, which is not answered within reasonable time. Protocol Protocol CAN bus: Protocol OFF / CANopen / LeoPC The CAN bus of this unit may be operated with different protocols and Baud rates. This parameter defines the protocol to be utilized. Please note, that all participants on the CAN bus must use the same protocol. CL2 3155 DE EN OFF ..............The CAN bus is disconnected. Values are not sent or received. CANopen .....The CANopen protocol is used. LeoPC ..........The CAN CAL protocol is used. CL2 3156 Page 34/83 Baudrate Baudrate CAN bus: Baudrate 20 / 50 / 100 / 125 / 250 / 500 / 800 / 1,000 kBaud The CAN bus of this unit may be operated with different protocols and Baud rates. This parameter defines the used Baud rate. Please note, that all participants on the CAN bus must use the same Baud rate. © Woodward