Download Caution! - Moeller
Transcript
03/09 AWB2723-1617en What Happens If …? Behaviour of the SWD power feeder modules The status of an SWD power feed module EU5C-SWD-PF1-1 or EU5C-SWD-PF2-1 is signalled optically via the front panel LED POW. Event Explanation Remedy LED off No 15 V DC device voltage available or the LED is defective. Check the POW power supply or the SWD power feed module LED yellow continuous light 1) 15-V-DC device voltage OK. - Behaviour of the SWD inputs/outputs modules The status of an SWD I/O module is signalled optically via the green front panel LED SWD. Table 24: Diagnosis of an SWD I/O module with the aid of the green SWD LED Event Explanation Remedy LED off No 15 V DC device voltage via the SWD network or the I/O module or the LED is defective. Check the power supply or I/O module. LED green continuous light 1) Fault-free operation, data exchange OK. - LED green flashing (1 Hz) No data exchange with the SWD gateway. The I/O module may not be in the target configuration or the SWD gateway is just creating a target configuration. LED green fast flashing (3 Hz) Error in the I/O module, e.g. overload. Determine or evaluate the defect by means of a detailed slave diagnosis in the control program. The I/O module indicates the statuses of its input and/or outputs with yellow LEDs. 118