outer two terminals of the regen connector, as shown below. If
the wire or connector are missing, remove power from the drive
and replace them.
If the internal resistor is connected and you still experience regen
faults on your BLU-AC, you’
ll need to connect a larger resistor
externally. You also must inform the drive that you’
ve done this,
by selecting the “external”option button. Then you must enter the
continuous power capacity, in watts, and the resistance. Now for
the hard part: entering the number of seconds that the peak
regen power level can be sustained by your external resistor. The
peak regen power is 160,000 / R where R is the resistance of
your external resistor. For a 50 ohm resistor, the peak power is
3200 watts. The resistor manufacturer can help you with this.
Consult the hardware manual when connecting the external resistor to the drive.
Reset Factory Defaults
If things really get out of hand, you can click this button to return the drive to the way it was when we shipped
it from the factory.
Alarm History
This provides the same view of recent alarms and faults as the button on the main Mis Programmer screen.
Please see page 21.
Configure I/O
This activates the same dialog as the Configure I/O button on the main Mis Programmer screen. Please refer
to page 17.
The Tuning - Sampling Tab
This tab allows you to set the control loop parameters (also called servo gains) and adjust the filters. You can
also experiment with the response to your choices of gains and filter settings using a built-in digital scope.
The Scope
At some point, you are going to want to observe how well your choice of gain parameters works. We have
included a sampling oscilloscope feature for this reason. All you have to do is select the move profile you’
d
like to try, by entering a move distance, a maximum speed, and the acceleration rate. You should select a
move that is meaningful to your application. There is no point in optimizing your speed around 50 rev/sec if
your application only calls for speeds of 10 rps. The same is true for distance and acceleration.
The oscilloscope window can display either one or two measurements at a time. The choices include Actual
Speed, Target Speed, Position Error, Current Command and Actual Position. The drive only samples what
you have selected, so if you change plot parameters you must sample again to update the display. By making
the oscilloscope “full screen”you can get a better display resolution and see your move in more detail.
You may also choose clockwise or counterclockwise rotation. If your load is vertical, you may want to observe
the differences. If your load is linear, then you can’
t keep sampling in the same direction or you’
ll run out of
travel. For applications where travel is limited, choose “alternate direction.”Then the drive will change the
direction after each move.