Download Full Text

Transcript
ABSTRACT
Dynamic loading is the term used for one way of optimally loading a transformer.
Dynamic loading means the utility takes into account the thermal time constant of the
transformer along with the cooling mode transitions, loading profile and ambient
temperature when determining the time-varying loading capability of a transformer.
Knowing the maximum dynamic loading rating can increase utilization of the
transformer while not reducing life-expectancy, delaying the replacement of the
transformer. This document presents the progress on the transformer dynamic loading
project sponsored by Salt River Project (SRP). A software application which performs
dynamic loading for substation distribution transformers with appropriate transformer
thermal models is developed in this project.
Two kinds of thermal hottest-spot temperature (HST) and top-oil temperature
(TOT) models that will be used in the application—the ASU HST/TOT models and the
ANSI models—are presented. Brief validations of the ASU models are presented,
showing that the ASU models are accurate in simulating the thermal processes of the
transformers. For this production grade application, both the ANSI and the ASU
models are built and tested to select the most appropriate models to be used in the
dynamic loading calculations.
An existing application to build and select the TOT model was used as a starting
point for the enhancements developed in this work. These enhancements include:

Adding the ability to develop HST models to the existing application,

Adding metrics to evaluate the models accuracy and selecting which
model will be used in dynamic loading calculation

Adding the capability to perform dynamic loading calculations,
iii