System Point Description Modbus Slave Address Point Number 52014 Point Type 16-bit unsigned integer The rules that determine how the Modbus Slave driver responds to requests according to the specified slave address are detailed as follows: • Responses are sent to serial Modbus requests that include a slave address that matches the Modbus Slave Address configured value in the RTU. • If the slave address included in the request is zero, i.e. broadcast address, the Modbus Slave will respond irrespective of the configuration value of the Modbus Slave Address. • If the specified slave address is non-zero AND differs from the configuration value, no response is sent for the request. The default value of the Slave Address is 1. It may be adjusted by the user or specified in an RTU configuration, and is a non-volatile RTU system point that is retained by the RTU. Changes in the Slave Address take effect when the RTU is restarted. Valid Slave Address configuration values are in the range of 1 – 247. SCADAPack E Series Modbus PLC ISaGRAF Interface Reference January 19, 2006 55