Chapter 9: Maintenance and Troubleshooting
Test Displays: With the Handheld Programmer you also have a more detailed display when
you use TEST Mode. For some instructions, the TEST-RUN mode display is more detailed
than the status displays shown in RUN mode. The following diagram shows an example of a
Timer instruction display during TEST-RUN mode.
RUN Mode
TMR T0 K1000
TEST-RUN Mode
S
S
T0 Contact (S is off)
(is on)
Current Value
Input to Timer
Maintenance
and Troubleshooting
T0 Contact (S is off)
(is on)
1425
TMR T0 K1000
Holding Output States: The ability to hold output states is very useful because it allows you
to maintain key system I/O points. In some cases, you may need to modify the program, but
you do not want certain operations to stop. In normal Run Mode, the outputs are turned off
when you return to Program Mode. In TEST-RUN mode, you can set each individual output
to either turn off, or to hold its last output state on the transition to TEST-PGM mode. You
can use AUX 58 on the Handheld Programmer to select the action for each individual
output. This feature is also available via a menu option within DirectSOFT. The following
diagram shows the differences between RUN and TEST-RUN modes.
RUN Mode to PGM Mode
X0
X1
Status on final scan
X0
X1
X4
Y0
Y1
END
X4
X10
Y0
Outputs are
OFF
Y1
END
TEST-RUN to TEST-PGM
Y0
X0
X2
X1
X10
X3
X4
Let Y1 turn
OFF
Hold Y0 ON
Y1
END
Maintenance
and Troubleshooting
X10
X2
X3
X2
X3
Before you decide that Test Mode is the perfect choice, remember that the DL205 CPUs also
allow you to edit the program during Run Mode. The primary difference between the Test
Modes and the Run Time Edit feature is you do not have to configure each individual I/O
point to hold the output status. When you use Run Time Edits, the CPU automatically
maintains all outputs in their current states while the program is being updated.
DL205 User Manual, 4th Edition, Rev. B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D