UPS
Battery cabinet No. 1 Battery cabinet No. 2
Fig.14. Connection example between a UPS and two battery cabinets.
4.3.6
COM port to relay. Connector (X32).

The communications line (COM) represents a very low safety voltage circuit. To maintain the quality, it
must be installed away from other lines that have dangerous voltages (power distribution line).

The communication port to relays provides digital signals in the form of potential free contacts with a
maximum applicable voltage and current of 6 A 30 V DC or 6 A 100 V AC. Both channels are used to
connect the UPS to any machine or device that has this standard bus (connector DB9 (X32)).

In standard units, there are 5 output signalling relays (one of which can be configured), whose common
point is connected to pin 5. Also an input signal can be externally supplied to perform Shutdown (5V~12V).

The most common use of these kinds of port is to supply the necessary information to the file closing
software.
Fig.15. DB9 Connector (X31) & (X32).
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 06 11 AA 59 201 02