CHAPTER 11: The Computational Fluid Dynamics Module
designer's database. For example, in figure 11.94, pipe sizes 2 1/2" and 3 1/2"
have been de-selected and therefore will not be used in any of the auto designs.
Fig. 11.94 Selecting Pipes to Exclude From the Design Optimizer
Calculating Results with the GHX Header Design Optimizer
The designer may now return to the Layout tab, select the Purge Results Type
from the dropdown menu and hit the 'Calculate' button again. Results from the 8
GHX Circuit GHX Module described in figure 11.87 above are available for view
in figure 11.95 below.
Notice how now the circuits and header sections all have velocities that are at 2
ft/s or higher. Also notice that the header pipe sizes have changed. In the previous
example (figure xx) and before the GHX Header Design Optimizer tool was used,
all the header pipes were 2" on the supply and return side. Now, the optimized
reverse-return headering system has reducing headers that start at GHX Header
Section #5 (highlighted) with a 1 1/2" pipe and reduce down to a final 3/4" header
section.
Notice also the Header sizes in the Pipe 2 (return pipe) column. They start out at
the top with a 3/4' diameter pipe in GHX Header Section #1 and gradually
increase until reaching a steady state 2" diameter at GHX Header Section #4. In
the Header Sections, the Pipe 1 and Pipe 2 sizes are exact opposite/palindromes.
303