Horn
3.12 Signal module
Setting the I/O Address
You now set the I/O address as follows using the available switches:
● Select the I/O address, e.g. 180h; the address must not yet be in use on the PC concerned,
otherwise an I/O address conflict will result.
● Convert to binary notation (0001 1000 0000); the conversion is simplified by considering
each HEX digit as a 4-Bit block.
● Set and delete the individual address bits
CAUTION: The DIL switches do not cover the four least significant bits.
The example given (180h) therefore has the following switch positions (default setting):
Switch Pin
8
7
6
5
4
3
2
1
Address Pin
11
10
9
8
7
6
5
4
Position
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
Example for the Address 100H (0001 0000 0000)
Switch Pin
8
7
6
5
4
3
2
1
Address Pin
11
10
9
8
7
6
5
4
Position
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
See also
ISA Bus Signal Module (Page 143)
Structure of the Switches and Plug-In Jumpers with the ISA Bus (Page 147)
WinCC/Options for Process Control
System Manual, 02/2013, A5E32315704-AA