Horn 3.12 Signal module Setting the I/O Address You now set the I/O address as follows using the available switches: ● Select the I/O address, e.g. 180h; the address must not yet be in use on the PC concerned, otherwise an I/O address conflict will result. ● Convert to binary notation (0001 1000 0000); the conversion is simplified by considering each HEX digit as a 4-Bit block. ● Set and delete the individual address bits CAUTION: The DIL switches do not cover the four least significant bits. The example given (180h) therefore has the following switch positions (default setting): Switch Pin 8 7 6 5 4 3 2 1 Address Pin 11 10 9 8 7 6 5 4 Position OFF OFF OFF ON ON OFF OFF OFF Example for the Address 100H (0001 0000 0000) Switch Pin 8 7 6 5 4 3 2 1 Address Pin 11 10 9 8 7 6 5 4 Position OFF OFF OFF ON OFF OFF OFF OFF See also ISA Bus Signal Module (Page 143) Structure of the Switches and Plug-In Jumpers with the ISA Bus (Page 147) WinCC/Options for Process Control System Manual, 02/2013, A5E32315704-AA 149